Description
Measures temperature and humidity / output as 0 .. 10 V signal / compact
Modbus RTU interface / wall mounting
The humidity detector is used in HVAC technology to monitor humidity and temperature. The measured values are output by the humidity detector as a 0 … 10 V standard signal. In this compact humidity detector, air humidity and temperature are precisely determined using a semiconductor component. For commissioning, the humidity detector is supplied via a DC voltage. The measured variables are output via a two-wire line. All connections are made via screw contacts in the waterproof IP 65 housing. In addition to the output of the measurement signal as a 0 … 10 V signal, the measurement values can be output via the RS485 interface. This function is particularly useful if several measuring points are to be linked to one another during your home surveillance.
Highlights
– Humidity and temperature sensors
– 0 … 10 V output
– simple wall mounting
– RS-485 interface
– for permanent monitoring
– various filters available
– small dimensions – Modbus RTU
Specification
Technical data humidity sensor PCE-P18
humidity
| measuring range |
0 … 100% RH |
| accuracy |
± 2% (in the range 10% …. 90% RH)
± 3% (remaining range) |
| hysteresis |
± 1% RH |
temperature
| measuring range |
– 20 … 60 ° C |
| accuracy |
| ± 0.7% of the measuring range |
|
| temperature effect |
± 25% / 10 ° C |
Humidity sensor output
| analog output |
0 … 10 V |
| Data Interface |
RS-485 Modbus RTU |
| transfer mode |
8N1, 8N2, 8E1, 8O1 |
| baud rate |
4800 bps
9600 bps
19200 bps
38400 bps
57600 bit / s |
General technical data for humidity sensors
| supply voltage |
19 V … 30 V DC |
| power |
<1.5 W |
| ambient temperature |
– 30 ° C … 85 ° C |
| Max. humidity |
≤ 95% RH |
| preheat |
15 minutes |
| degree of protection |
IP 65 |
| Assembly |
wall mounting |
| Dimensions (wxhxd) |
> 35 x 58 x 118 mm |
| Weight |
125 g |