Specification
Technical data humidity sensor PCE-P18
humidity
| measuring range |
0 … 100% RH |
| accuracy |
± 2% (in the range 10% …. 90% RH)
± 3% (remaining range) |
| hysteresis |
± 1% RH |
temperature
| measuring range |
– 20 … 60 ° C |
| accuracy |
| ± 0.7% of the measuring range |
|
| temperature effect |
± 25% / 10 ° C |
Humidity sensor output
| analog output |
0 … 10 V |
| Data Interface |
RS-485 Modbus RTU |
| transfer mode |
8N1, 8N2, 8E1, 8O1 |
| baud rate |
4800 bps
9600 bps
19200 bps
38400 bps
57600 bit / s |
General technical data for humidity sensors
| supply voltage |
19 V … 30 V DC |
| power |
<1.5 W |
| ambient temperature |
– 30 ° C … 85 ° C |
| Max. humidity |
≤ 95% RH |
| preheat |
15 minutes |
| degree of protection |
IP 65 |
| Assembly |
wall mounting |
| Dimensions (wxhxd) |
> 35 x 58 x 118 mm |
| Weight |
125 g |
Highlights
– Humidity and temperature sensors
– 0 … 10 V output
– simple wall mounting
– RS-485 interface
– for permanent monitoring
– various filters available
– small dimensions – Modbus RTU
Description
Measures temperature and humidity / output as 0 .. 10 V signal / compact
Modbus RTU interface / wall mounting
The humidity detector is used in HVAC technology to monitor humidity and temperature. The measured values are output by the humidity detector as a 0 … 10 V standard signal. In this compact humidity detector, air humidity and temperature are precisely determined using a semiconductor component. For commissioning, the humidity detector is supplied via a DC voltage. The measured variables are output via a two-wire line. All connections are made via screw contacts in the waterproof IP 65 housing. In addition to the output of the measurement signal as a 0 … 10 V signal, the measurement values can be output via the RS485 interface. This function is particularly useful if several measuring points are to be linked to one another during your home surveillance.